Wire Size Chart
Quick reference: circuit rating to conductor size
Smallest size for a noncontinuous load, assuming 60°C terminations at or below 100 A and 75°C above 100 A, 30°C ambient and three current-carrying conductors. Confirm actual equipment and terminal ratings. Each rating links to its own page with the full correction chain.
| Circuit rating | Copper | Aluminum | Details |
|---|---|---|---|
| 15 A | 14 AWG | 12 AWG | 15 amp wire size |
| 20 A | 12 AWG | 10 AWG | 20 amp wire size |
| 25 A | 10 AWG | 10 AWG | 25 amp wire size |
| 30 A | 10 AWG | 8 AWG | 30 amp wire size |
| 35 A | 8 AWG | 8 AWG | 35 amp wire size |
| 40 A | 8 AWG | 6 AWG | 40 amp wire size |
| 45 A | 6 AWG | 4 AWG | 45 amp wire size |
| 50 A | 6 AWG | 4 AWG | 50 amp wire size |
| 60 A | 4 AWG | 3 AWG | 60 amp wire size |
| 70 A | 4 AWG | 2 AWG | 70 amp wire size |
| 80 A | 3 AWG | 1 AWG | 80 amp wire size |
| 90 A | 2 AWG | 1/0 AWG | 90 amp wire size |
| 100 A | 1 AWG | 1/0 AWG | 100 amp wire size |
| 125 A | 1 AWG | 2/0 AWG | 125 amp wire size |
| 150 A | 1/0 AWG | 3/0 AWG | 150 amp wire size |
| 200 A | 3/0 AWG | 250 kcmil | 200 amp wire size |
| 250 A | 250 kcmil | 350 kcmil | 250 amp wire size |
| 300 A | 350 kcmil | 500 kcmil | 300 amp wire size |
| 400 A | 600 kcmil | 1000 kcmil | 400 amp wire size |
AWG wire size chart
Circular-mil values are nominal table values and may be rounded; THHN/THWN-2 cross-section is the value used for conduit fill. Ampacity values are the base table before any correction factor is applied — see the full wire ampacity chart for the aluminum 60°C and 90°C columns.
The mm² column is geometry only. A size conversion is not a rating conversion, which is what the mm² to AWG chart explains.
| Size | mm² | Circular mils | THHN area (sq in) | Cu 60°C | Cu 75°C | Cu 90°C | Al 75°C |
|---|---|---|---|---|---|---|---|
| 14 | 2.08 | 4,110 | 0.0097 | 15 A | 20 A | 25 A | — |
| 12 | 3.31 | 6,530 | 0.0133 | 20 A | 25 A | 30 A | 20 A |
| 10 | 5.26 | 10,380 | 0.0211 | 30 A | 35 A | 40 A | 30 A |
| 8 | 8.37 | 16,510 | 0.0366 | 40 A | 50 A | 55 A | 40 A |
| 6 | 13.3 | 26,240 | 0.0507 | 55 A | 65 A | 75 A | 50 A |
| 4 | 21.15 | 41,740 | 0.0824 | 70 A | 85 A | 95 A | 65 A |
| 3 | 26.66 | 52,620 | 0.0973 | 85 A | 100 A | 115 A | 75 A |
| 2 | 33.63 | 66,360 | 0.1158 | 95 A | 115 A | 130 A | 90 A |
| 1 | 42.41 | 83,690 | 0.1562 | 110 A | 130 A | 145 A | 100 A |
| 1/0 | 53.51 | 105,600 | 0.1855 | 125 A | 150 A | 170 A | 120 A |
| 2/0 | 67.44 | 133,100 | 0.2223 | 145 A | 175 A | 195 A | 135 A |
| 3/0 | 85.03 | 167,800 | 0.2679 | 165 A | 200 A | 225 A | 155 A |
| 4/0 | 107.22 | 211,600 | 0.3237 | 195 A | 230 A | 260 A | 180 A |
| 250 | 126.68 | 250,000 | 0.397 | 215 A | 255 A | 290 A | 205 A |
| 300 | 152.01 | 300,000 | 0.4608 | 240 A | 285 A | 320 A | 230 A |
| 350 | 177.35 | 350,000 | 0.5242 | 260 A | 310 A | 350 A | 250 A |
| 400 | 202.68 | 400,000 | 0.5863 | 280 A | 335 A | 380 A | 270 A |
| 500 | 253.35 | 500,000 | 0.7073 | 320 A | 380 A | 430 A | 310 A |
| 600 | 304.02 | 600,000 | 0.8676 | 350 A | 420 A | 475 A | 340 A |
| 750 | 380.03 | 750,000 | 1.0496 | 400 A | 475 A | 535 A | 385 A |
| 1000 | 506.71 | 1,000,000 | 1.3478 | 455 A | 545 A | 615 A | 445 A |
How to read this chart
- Find the load first. Conductor size follows the overcurrent device and the load, not the other way round — a 20 A breaker with 14 AWG copper on it is a code violation even though the wire will physically carry the current for a while.
- Base ampacity is a starting point. Ambient temperature above 30°C and more than three current-carrying conductors in one raceway both reduce what the conductor may carry.
- Terminations can cap you below the insulation rating. A 90°C conductor on 60°C terminations is limited to the 60°C column.
- Voltage drop is a separate check. On long runs the voltage drop calculator often forces a larger size than ampacity alone would require.
Frequently asked
- What does AWG mean on a wire size chart?
- AWG stands for American Wire Gauge. It is an inverse scale: a smaller number is a larger conductor. 14 AWG carries less current than 8 AWG, and above 4/0 the chart switches to kcmil (thousands of circular mils), where the number is the area itself — 250 kcmil is 250,000 circular mils.
- What is the difference between AWG and kcmil?
- Both describe the same thing — conductor area — in different units. AWG is a gauge number for sizes up to 4/0; kcmil (also written MCM) is thousands of circular mils and is used for larger sizes. One circular mil is the area of a circle one thousandth of an inch across.
- Why does the chart show three ampacity columns?
- Because a conductor's allowable current depends on the temperature rating of its insulation. The same copper conductor appears in the 60°C, 75°C and 90°C columns with different values; you use the column that matches the insulation and the temperature rating of the terminations, not simply the highest number.
- Which column should I use for a typical branch circuit?
- For equipment rated 100 A or less, the 60°C column is the conservative starting assumption unless the applicable rules and equipment markings permit a higher rating. Verify both terminations, conductor insulation and installation conditions; apply adjustments as required.
- Does this chart apply to aluminum conductors?
- The aluminum column is shown for 75°C. Aluminum is generally one to two sizes larger than copper for the same current, and small aluminum sizes below 12 AWG are not covered. Confirm that the terminations you are using are listed for aluminum before mixing materials.
Table values reflect NEC 2023 and are pending review. Educational information only — not professional engineering advice. Verify before ordering cable.