Reference
Methodology & Sources
This page is rendered directly from the calculation core, so it cannot drift from the code.
Base edition: NEC 2023. The NEC table values on this site reflect NEC 2023. The 2026 edition and local amendments have not been verified. IEC tables: IEC 60364-5-52:2009+AC1:2011.
27 constants and where they come from
- AWG/kcmil conductor circular milsconfidence: physicalRef: Physical conversion: 1 mil = 0.001 in; circular mils = diameter (mil)^2verified: pending
- AWG/kcmil to mm² conversion (1 circular mil = 0.0005067074791 mm²)confidence: physicalRef: Physical conversion: 1 circular mil = pi/4 x (0.0254 mm)^2, since 1 mil = 0.001 inverified: pending
- Metric nominal cross-sectional area series (IEC 60228, 0.5 mm² to 1000 mm²)confidence: physicalRef: IEC 60228 nominal cross-sectional areasverified: pending
- IEC metric ampacity, copper with PVC insulation at 70°C (air, 30°C reference)confidence: code-tableRef: IEC 60364-5-52:2009 with AC1:2011, Tables B.52.2 (2 loaded conductors) and B.52.4 (3 loaded conductors)verified: pending
- IEC metric ampacity, copper with XLPE/EPR insulation at 90°C (air, 30°C reference)confidence: code-tableRef: IEC 60364-5-52:2009, Tables B.52.3 (2 loaded conductors) and B.52.5 (3 loaded conductors)verified: pending
- Voltage-drop resistance constant K (copper 12.9 / aluminum 21.2 ohm-cmil/ft)confidence: engineeringRef: Derived from NEC Chapter 9, Table 8 resistance values; common engineering approximationverified: pending
- Conductor ampacity base table (60/75/90°C)confidence: code-tableRef: NEC 310.16verified: pending
- Ambient temperature correction factor, 30°C baseconfidence: code-tableRef: NEC Table 310.15(B)(1)(1)verified: pending
- Adjustment factor for conductor count in a racewayconfidence: code-tableRef: NEC 310.15(C)(1)verified: pending
- Termination temperature limit (explicit 60°C or 75°C column)confidence: code-tableRef: NEC 110.14(C)verified: pending
- Conduit fill percentage (1 conductor 53% / 2 conductors 31% / 3 or more 40%)confidence: code-tableRef: NEC Chapter 9, Table 1 and Note 7verified: pending
- Conduit internal diameter and total internal areaconfidence: code-tableRef: NEC Chapter 9, Table 4verified: pending
- Conductor cross-sectional area (THHN/THWN and similar)confidence: code-tableRef: NEC Chapter 9, Table 5verified: pending
- Box volume allowances and minimum box volume requirementsconfidence: code-tableRef: NEC 314.16verified: pending
- Standard overcurrent protective device ratingsconfidence: code-tableRef: NEC 240.6(A)verified: pending
- Small-conductor overcurrent protection limits (14/12/10 AWG)confidence: code-tableRef: NEC 240.4(D)verified: pending
- Continuous loads: 125% for the overcurrent device and the termination column, 100% for corrected ampacityconfidence: code-tableRef: NEC 210.20(A)verified: pending
- Branch-circuit voltage drop recommendation of 3% or less, and 5% combined (informational note)confidence: code-tableRef: NEC 210.19(A)(1) Informational Noteverified: pending
- Recessed light count and spacing (target fc x area / (lumens x CU x LLF))confidence: engineeringRef: Lighting design arithmetic; the rule-of-thumb spacing is half the ceiling height and is not an NEC requirementverified: pending
- Conditional next-higher standard overcurrent device exceptionconfidence: code-tableRef: NEC 240.4(B)verified: pending
- IEC metric ampacity, aluminium, verified from 16 mm²confidence: code-tableRef: IEC 60364-5-52:2009, Tables B.52.2 to B.52.5verified: pending
- IEC air ambient-temperature correction factorsconfidence: code-tableRef: IEC 60364-5-52:2009, Table B.52.14verified: pending
- IEC grouping correction factors for circuits in airconfidence: code-tableRef: IEC 60364-5-52:2009, Table B.52.17verified: pending
- IEC soil-temperature correction factors for buried cablesconfidence: code-tableRef: IEC 60364-5-52:2009, Table B.52.15verified: pending
- IEC grouping factors for buried multi-core cables, method D2confidence: code-tableRef: IEC 60364-5-52:2009, Table B.52.18verified: pending
- IEC grouping factors for buried ducts, method D1confidence: code-tableRef: IEC 60364-5-52:2009, Table B.52.19verified: pending
- Feeder voltage drop recommendation of 3% or less, and 5% combined (informational note)confidence: code-tableRef: NEC 215.2(A)(1) Informational Noteverified: pending