Electrical Quick Reference
Conductor sizes, areas and base ampacity
Ampacity columns are base table values: 30°C ambient, three or fewer current-carrying conductors, before any termination limit. Apply the corrections below before using them.
| Size | mm² | Circular mils | THHN area (sq in) | Cu 60°C | Cu 75°C | Cu 90°C | Al 75°C |
|---|---|---|---|---|---|---|---|
| 14 | 2.08 | 4,110 | 0.0097 | 15 A | 20 A | 25 A | — |
| 12 | 3.31 | 6,530 | 0.0133 | 20 A | 25 A | 30 A | 20 A |
| 10 | 5.26 | 10,380 | 0.0211 | 30 A | 35 A | 40 A | 30 A |
| 8 | 8.37 | 16,510 | 0.0366 | 40 A | 50 A | 55 A | 40 A |
| 6 | 13.3 | 26,240 | 0.0507 | 55 A | 65 A | 75 A | 50 A |
| 4 | 21.15 | 41,740 | 0.0824 | 70 A | 85 A | 95 A | 65 A |
| 3 | 26.66 | 52,620 | 0.0973 | 85 A | 100 A | 115 A | 75 A |
| 2 | 33.63 | 66,360 | 0.1158 | 95 A | 115 A | 130 A | 90 A |
| 1 | 42.41 | 83,690 | 0.1562 | 110 A | 130 A | 145 A | 100 A |
| 1/0 | 53.51 | 105,600 | 0.1855 | 125 A | 150 A | 170 A | 120 A |
| 2/0 | 67.44 | 133,100 | 0.2223 | 145 A | 175 A | 195 A | 135 A |
| 3/0 | 85.03 | 167,800 | 0.2679 | 165 A | 200 A | 225 A | 155 A |
| 4/0 | 107.22 | 211,600 | 0.3237 | 195 A | 230 A | 260 A | 180 A |
| 250 | 126.68 | 250,000 | 0.397 | 215 A | 255 A | 290 A | 205 A |
| 300 | 152.01 | 300,000 | 0.4608 | 240 A | 285 A | 320 A | 230 A |
| 350 | 177.35 | 350,000 | 0.5242 | 260 A | 310 A | 350 A | 250 A |
| 400 | 202.68 | 400,000 | 0.5863 | 280 A | 335 A | 380 A | 270 A |
| 500 | 253.35 | 500,000 | 0.7073 | 320 A | 380 A | 430 A | 310 A |
| 600 | 304.02 | 600,000 | 0.8676 | 350 A | 420 A | 475 A | 340 A |
| 750 | 380.03 | 750,000 | 1.0496 | 400 A | 475 A | 535 A | 385 A |
| 1000 | 506.71 | 1,000,000 | 1.3478 | 455 A | 545 A | 615 A | 445 A |
Reference: NEC 310.16 (ampacity); NEC Chapter 9, Table 5 (THHN area); geometry (mm²)
Conduit fill: how many 12 AWG THHN conductors fit
Each count is the largest number of identical THHN/THWN-2 conductors that Chapter 9, Table 1 and Note 7 permit: 53% for one, 31% for two, and 40% for three or more. A decimal fraction of 0.8 or larger rounds up. The equipment grounding conductor is not included. A thicker insulation takes more space.
| Trade size | EMT | PVC40 | RMC | IMC |
|---|---|---|---|---|
| 1/2 in | 9 | 8 | 9 | 10 |
| 3/4 in | 16 | 15 | 16 | 17 |
| 1 in | 26 | 25 | 26 | 29 |
| 1-1/4 in | 45 | 43 | 46 | 49 |
| 1-1/2 in | 61 | 59 | 62 | 67 |
| 2 in | 101 | 99 | 102 | 109 |
| 2-1/2 in | 176 | 141 | 146 | 154 |
| 3 in | 266 | 218 | 225 | 238 |
| 3-1/2 in | 347 | 293 | 301 | 318 |
| 4 in | 443 | 377 | 387 | 410 |
Reference: NEC Chapter 9, Table 1 (fill limits) and Table 4 (conduit internal area)
Ambient temperature correction factors
Multiply the base ampacity by the factor in the row for the ambient temperature the raceway actually runs through.
| Ambient | 60°C conductor | 75°C conductor | 90°C conductor |
|---|---|---|---|
| 10 or less | x 1.29 | x 1.2 | x 1.15 |
| 11–15 | x 1.22 | x 1.15 | x 1.12 |
| 16–20 | x 1.15 | x 1.11 | x 1.08 |
| 21–25 | x 1.08 | x 1.05 | x 1.04 |
| 26–30 | x 1 | x 1 | x 1 |
| 31–35 | x 0.91 | x 0.94 | x 0.96 |
| 36–40 | x 0.82 | x 0.88 | x 0.91 |
| 41–45 | x 0.71 | x 0.82 | x 0.87 |
| 46–50 | x 0.58 | x 0.75 | x 0.82 |
| 51–55 | x 0.41 | x 0.67 | x 0.76 |
| 56–60 | — | x 0.58 | x 0.71 |
| 61–65 | — | x 0.47 | x 0.65 |
| 66–70 | — | x 0.33 | x 0.58 |
| 71–75 | — | — | x 0.5 |
| 76–80 | — | — | x 0.41 |
| 81–85 | — | — | x 0.29 |
Reference: NEC Table 310.15(B)(1)(1)
Conductor-count adjustment factors
Applies once more than three current-carrying conductors share a raceway. The equipment grounding conductor does not count here, but it does count for conduit fill.
| Current-carrying conductors | Factor |
|---|---|
| 4–6 | x 0.8 |
| 7–9 | x 0.7 |
| 10–20 | x 0.5 |
| 21–30 | x 0.45 |
| 31–40 | x 0.4 |
| 41 or more | x 0.35 |
Reference: NEC 310.15(C)(1)
Voltage drop at 120 V, 15 A, single phase
Copper conductors, one-way lengths, computed with the resistance constant K. The feeder and branch-circuit recommendation is 3% or less; the combined path is 5%.
| Size | 50 ft | 100 ft | 150 ft |
|---|---|---|---|
| 14 AWG (2.08 mm²) | 3.92 % | 7.85 % | 11.77 % |
| 12 AWG (3.31 mm²) | 2.47 % | 4.94 % | 7.41 % |
| 10 AWG (5.26 mm²) | 1.55 % | 3.11 % | 4.66 % |
| 8 AWG (8.37 mm²) | 0.98 % | 1.95 % | 2.93 % |
| 6 AWG (13.3 mm²) | 0.61 % | 1.23 % | 1.84 % |
Reference: K derived from NEC Chapter 9, Table 8; 3% recommendation from NEC 210.19(A)(1) Informational Note
Copper cable capacity by nominal size (IEC)
Tabulated capacities at the reference conditions: reference method C, air at 30°C, single circuit, no grouping. Method C is cable clipped direct. Within the air methods on this page (A1 to C) it is the highest; the buried methods D1 and D2 use a 20°C soil reference and can exceed C at small sizes, and the free-air E, F and G methods are higher still but are not included here. Values are taken from IEC 60364-5-52:2009. The 2024 consolidated edition has not been checked for changes to these tables — verify against the edition in force where the installation will be inspected.
| Size | PVC, 2 loaded | PVC, 3 loaded | XLPE, 2 loaded | XLPE, 3 loaded |
|---|---|---|---|---|
| 1.5 mm² | 19.5 A | 17.5 A | 24 A | 22 A |
| 2.5 mm² | 27 A | 24 A | 33 A | 30 A |
| 4 mm² | 36 A | 32 A | 45 A | 40 A |
| 6 mm² | 46 A | 41 A | 58 A | 52 A |
| 10 mm² | 63 A | 57 A | 80 A | 71 A |
| 16 mm² | 85 A | 76 A | 107 A | 96 A |
| 25 mm² | 112 A | 96 A | 138 A | 119 A |
| 35 mm² | 138 A | 119 A | 171 A | 147 A |
| 50 mm² | 168 A | 144 A | 209 A | 179 A |
| 70 mm² | 213 A | 184 A | 269 A | 229 A |
| 95 mm² | 258 A | 223 A | 328 A | 278 A |
| 120 mm² | 299 A | 259 A | 382 A | 322 A |
| 150 mm² | 344 A | 299 A | 441 A | 371 A |
| 185 mm² | 392 A | 341 A | 506 A | 424 A |
| 240 mm² | 461 A | 403 A | 599 A | 500 A |
| 300 mm² | 530 A | 464 A | 693 A | 576 A |
Reference: IEC 60364-5-52:2009, Tables B.52.2 / B.52.3 (2 loaded conductors) and B.52.4 / B.52.5 (3 loaded conductors)
Aluminum cable capacity by nominal size (IEC)
Tabulated capacities at the reference conditions: reference method C, air at 30°C, single circuit, no grouping. Method C is cable clipped direct. Within the air methods on this page (A1 to C) it is the highest; the buried methods D1 and D2 use a 20°C soil reference and can exceed C at small sizes, and the free-air E, F and G methods are higher still but are not included here. Values are taken from IEC 60364-5-52:2009. The 2024 consolidated edition has not been checked for changes to these tables — verify against the edition in force where the installation will be inspected.
| Size | PVC, 2 loaded | PVC, 3 loaded | XLPE, 2 loaded | XLPE, 3 loaded |
|---|---|---|---|---|
| 16 mm² | 66 A | 59 A | 84 A | 76 A |
| 25 mm² | 83 A | 73 A | 101 A | 90 A |
| 35 mm² | 103 A | 90 A | 126 A | 112 A |
| 50 mm² | 125 A | 110 A | 154 A | 136 A |
| 70 mm² | 160 A | 140 A | 198 A | 174 A |
| 95 mm² | 195 A | 170 A | 241 A | 211 A |
| 120 mm² | 226 A | 197 A | 280 A | 245 A |
| 150 mm² | 261 A | 227 A | 324 A | 283 A |
| 185 mm² | 298 A | 259 A | 371 A | 323 A |
| 240 mm² | 352 A | 305 A | 439 A | 382 A |
| 300 mm² | 406 A | 351 A | 508 A | 440 A |
Reference: IEC 60364-5-52:2009, Tables B.52.2 / B.52.3 (2 loaded conductors) and B.52.4 / B.52.5 (3 loaded conductors)
Ambient temperature correction, air (IEC)
Multiply the tabulated capacity by the factor for the ambient the cable actually runs through. Above the tabulated range the standard gives no value.
| Ambient | PVC (70°C) | XLPE (90°C) |
|---|---|---|
| up to 10°C | x 1.22 | x 1.15 |
| up to 15°C | x 1.17 | x 1.12 |
| up to 20°C | x 1.12 | x 1.08 |
| up to 25°C | x 1.06 | x 1.04 |
| up to 30°C | x 1 | x 1 |
| up to 35°C | x 0.94 | x 0.96 |
| up to 40°C | x 0.87 | x 0.91 |
| up to 45°C | x 0.79 | x 0.87 |
| up to 50°C | x 0.71 | x 0.82 |
| up to 55°C | x 0.61 | x 0.76 |
| up to 60°C | x 0.5 | x 0.71 |
| up to 65°C | — | x 0.65 |
| up to 70°C | — | x 0.58 |
| up to 75°C | — | x 0.5 |
| up to 80°C | — | x 0.41 |
Reference: IEC 60364-5-52:2009, Table B.52.14 (air, 30°C reference)
Educational and design-planning reference only — not professional engineering advice. NEC table values reflect NEC 2023 and are pending review; the 2026 edition has not been verified. Installation must be carried out by a licensed electrician in accordance with the code enforced locally.
Frequently asked
- What is on this sheet?
- Conductor sizes with mm², circular mils and THHN area plus base ampacity; how many 12 AWG THHN conductors fit each trade size; the ambient temperature and conductor-count correction factors; voltage drop on 120 V circuits; and the IEC tabulated capacities for metric cable, with the PVC and XLPE columns side by side. Every table prints the clause it comes from.
- Do the ampacity columns include the correction factors?
- No. They are base table values: 30°C ambient, three or fewer current-carrying conductors and no termination limit. Apply the ambient factor and the conductor-count factor printed on the same sheet, then cap the result at the termination value for the equipment you have.
- Can I use the IEC table for a North American job, or the NEC table in Europe?
- No. The two sets are not interchangeable. They rest on different installation methods, reference conditions and grouping rules, so a number lifted from one cannot stand in for the other. Use the table that belongs to the standard your installation is inspected against — both are printed here so nothing has to be converted by hand.
- Is the metric table just the AWG column converted?
- No. A mm² to AWG conversion is geometry only: it compares cross-sectional areas. The IEC capacities depend on insulation, installation method, ambient temperature and grouping, which is why they are printed as their own table. For the conversion itself, use the mm² to AWG chart.
- Can I print it, or hand it to someone else?
- Yes. The sheet is free, needs no signup and prints on landscape A4 or Letter; the PDF is generated in the browser, so nothing is uploaded. If you pass it on, a link back to this page is appreciated and keeps the version current.
- How are the values produced?
- Every cell is computed by this site's calculation engine from registered constants rather than typed by hand, so the page, the PDF and the calculators cannot drift apart. The methodology page lists each source, its clause and its review status.
Sources, clauses and review status for every constant are on the methodology page.
Use the numbers in a calculator
- Voltage drop calculator
- Conduit fill calculator
- Ampacity calculator
- Wire size calculator
- Conduit fill chart
- Wire size chart
- NEC ampacity chart
- Cable size calculator (IEC, mm²)
- mm² to AWG chart
Prefer the numbers in context? The correction-factor guide works through the same table step by step.