Reference

Electrical Quick Reference

One page of the numbers that come up constantly on the job: conductor areas, base ampacity, conduit fill counts, correction factors and voltage drop — in AWG/kcmil and in mm². The NEC tables and the IEC tables are kept separate on purpose: the two systems assume different installation conditions and are not interchangeable. Every figure is computed live by the same engine as the calculators, and every table names the clause it comes from.

Conductor sizes, areas and base ampacity

Ampacity columns are base table values: 30°C ambient, three or fewer current-carrying conductors, before any termination limit. Apply the corrections below before using them.

Sizemm²Circular milsTHHN area (sq in)Cu 60°CCu 75°CCu 90°CAl 75°C
142.084,1100.009715 A20 A25 A—
123.316,5300.013320 A25 A30 A20 A
105.2610,3800.021130 A35 A40 A30 A
88.3716,5100.036640 A50 A55 A40 A
613.326,2400.050755 A65 A75 A50 A
421.1541,7400.082470 A85 A95 A65 A
326.6652,6200.097385 A100 A115 A75 A
233.6366,3600.115895 A115 A130 A90 A
142.4183,6900.1562110 A130 A145 A100 A
1/053.51105,6000.1855125 A150 A170 A120 A
2/067.44133,1000.2223145 A175 A195 A135 A
3/085.03167,8000.2679165 A200 A225 A155 A
4/0107.22211,6000.3237195 A230 A260 A180 A
250126.68250,0000.397215 A255 A290 A205 A
300152.01300,0000.4608240 A285 A320 A230 A
350177.35350,0000.5242260 A310 A350 A250 A
400202.68400,0000.5863280 A335 A380 A270 A
500253.35500,0000.7073320 A380 A430 A310 A
600304.02600,0000.8676350 A420 A475 A340 A
750380.03750,0001.0496400 A475 A535 A385 A
1000506.711,000,0001.3478455 A545 A615 A445 A

Reference: NEC 310.16 (ampacity); NEC Chapter 9, Table 5 (THHN area); geometry (mm²)

Conduit fill: how many 12 AWG THHN conductors fit

Each count is the largest number of identical THHN/THWN-2 conductors that Chapter 9, Table 1 and Note 7 permit: 53% for one, 31% for two, and 40% for three or more. A decimal fraction of 0.8 or larger rounds up. The equipment grounding conductor is not included. A thicker insulation takes more space.

Trade sizeEMTPVC40RMCIMC
1/2 in98910
3/4 in16151617
1 in26252629
1-1/4 in45434649
1-1/2 in61596267
2 in10199102109
2-1/2 in176141146154
3 in266218225238
3-1/2 in347293301318
4 in443377387410

Reference: NEC Chapter 9, Table 1 (fill limits) and Table 4 (conduit internal area)

Ambient temperature correction factors

Multiply the base ampacity by the factor in the row for the ambient temperature the raceway actually runs through.

Ambient60°C conductor75°C conductor90°C conductor
10 or lessx 1.29x 1.2x 1.15
11–15x 1.22x 1.15x 1.12
16–20x 1.15x 1.11x 1.08
21–25x 1.08x 1.05x 1.04
26–30x 1x 1x 1
31–35x 0.91x 0.94x 0.96
36–40x 0.82x 0.88x 0.91
41–45x 0.71x 0.82x 0.87
46–50x 0.58x 0.75x 0.82
51–55x 0.41x 0.67x 0.76
56–60—x 0.58x 0.71
61–65—x 0.47x 0.65
66–70—x 0.33x 0.58
71–75——x 0.5
76–80——x 0.41
81–85——x 0.29

Reference: NEC Table 310.15(B)(1)(1)

Conductor-count adjustment factors

Applies once more than three current-carrying conductors share a raceway. The equipment grounding conductor does not count here, but it does count for conduit fill.

Current-carrying conductorsFactor
4–6x 0.8
7–9x 0.7
10–20x 0.5
21–30x 0.45
31–40x 0.4
41 or morex 0.35

Reference: NEC 310.15(C)(1)

Voltage drop at 120 V, 15 A, single phase

Copper conductors, one-way lengths, computed with the resistance constant K. The feeder and branch-circuit recommendation is 3% or less; the combined path is 5%.

Size50 ft100 ft150 ft
14 AWG (2.08 mm²)3.92 %7.85 %11.77 %
12 AWG (3.31 mm²)2.47 %4.94 %7.41 %
10 AWG (5.26 mm²)1.55 %3.11 %4.66 %
8 AWG (8.37 mm²)0.98 %1.95 %2.93 %
6 AWG (13.3 mm²)0.61 %1.23 %1.84 %

Reference: K derived from NEC Chapter 9, Table 8; 3% recommendation from NEC 210.19(A)(1) Informational Note

Copper cable capacity by nominal size (IEC)

Tabulated capacities at the reference conditions: reference method C, air at 30°C, single circuit, no grouping. Method C is cable clipped direct. Within the air methods on this page (A1 to C) it is the highest; the buried methods D1 and D2 use a 20°C soil reference and can exceed C at small sizes, and the free-air E, F and G methods are higher still but are not included here. Values are taken from IEC 60364-5-52:2009. The 2024 consolidated edition has not been checked for changes to these tables — verify against the edition in force where the installation will be inspected.

SizePVC, 2 loadedPVC, 3 loadedXLPE, 2 loadedXLPE, 3 loaded
1.5 mm²19.5 A17.5 A24 A22 A
2.5 mm²27 A24 A33 A30 A
4 mm²36 A32 A45 A40 A
6 mm²46 A41 A58 A52 A
10 mm²63 A57 A80 A71 A
16 mm²85 A76 A107 A96 A
25 mm²112 A96 A138 A119 A
35 mm²138 A119 A171 A147 A
50 mm²168 A144 A209 A179 A
70 mm²213 A184 A269 A229 A
95 mm²258 A223 A328 A278 A
120 mm²299 A259 A382 A322 A
150 mm²344 A299 A441 A371 A
185 mm²392 A341 A506 A424 A
240 mm²461 A403 A599 A500 A
300 mm²530 A464 A693 A576 A

Reference: IEC 60364-5-52:2009, Tables B.52.2 / B.52.3 (2 loaded conductors) and B.52.4 / B.52.5 (3 loaded conductors)

Aluminum cable capacity by nominal size (IEC)

Tabulated capacities at the reference conditions: reference method C, air at 30°C, single circuit, no grouping. Method C is cable clipped direct. Within the air methods on this page (A1 to C) it is the highest; the buried methods D1 and D2 use a 20°C soil reference and can exceed C at small sizes, and the free-air E, F and G methods are higher still but are not included here. Values are taken from IEC 60364-5-52:2009. The 2024 consolidated edition has not been checked for changes to these tables — verify against the edition in force where the installation will be inspected.

SizePVC, 2 loadedPVC, 3 loadedXLPE, 2 loadedXLPE, 3 loaded
16 mm²66 A59 A84 A76 A
25 mm²83 A73 A101 A90 A
35 mm²103 A90 A126 A112 A
50 mm²125 A110 A154 A136 A
70 mm²160 A140 A198 A174 A
95 mm²195 A170 A241 A211 A
120 mm²226 A197 A280 A245 A
150 mm²261 A227 A324 A283 A
185 mm²298 A259 A371 A323 A
240 mm²352 A305 A439 A382 A
300 mm²406 A351 A508 A440 A

Reference: IEC 60364-5-52:2009, Tables B.52.2 / B.52.3 (2 loaded conductors) and B.52.4 / B.52.5 (3 loaded conductors)

Ambient temperature correction, air (IEC)

Multiply the tabulated capacity by the factor for the ambient the cable actually runs through. Above the tabulated range the standard gives no value.

AmbientPVC (70°C)XLPE (90°C)
up to 10°Cx 1.22x 1.15
up to 15°Cx 1.17x 1.12
up to 20°Cx 1.12x 1.08
up to 25°Cx 1.06x 1.04
up to 30°Cx 1x 1
up to 35°Cx 0.94x 0.96
up to 40°Cx 0.87x 0.91
up to 45°Cx 0.79x 0.87
up to 50°Cx 0.71x 0.82
up to 55°Cx 0.61x 0.76
up to 60°Cx 0.5x 0.71
up to 65°C—x 0.65
up to 70°C—x 0.58
up to 75°C—x 0.5
up to 80°C—x 0.41

Reference: IEC 60364-5-52:2009, Table B.52.14 (air, 30°C reference)

Educational and design-planning reference only — not professional engineering advice. NEC table values reflect NEC 2023 and are pending review; the 2026 edition has not been verified. Installation must be carried out by a licensed electrician in accordance with the code enforced locally.

Frequently asked

What is on this sheet?
Conductor sizes with mm², circular mils and THHN area plus base ampacity; how many 12 AWG THHN conductors fit each trade size; the ambient temperature and conductor-count correction factors; voltage drop on 120 V circuits; and the IEC tabulated capacities for metric cable, with the PVC and XLPE columns side by side. Every table prints the clause it comes from.
Do the ampacity columns include the correction factors?
No. They are base table values: 30°C ambient, three or fewer current-carrying conductors and no termination limit. Apply the ambient factor and the conductor-count factor printed on the same sheet, then cap the result at the termination value for the equipment you have.
Can I use the IEC table for a North American job, or the NEC table in Europe?
No. The two sets are not interchangeable. They rest on different installation methods, reference conditions and grouping rules, so a number lifted from one cannot stand in for the other. Use the table that belongs to the standard your installation is inspected against — both are printed here so nothing has to be converted by hand.
Is the metric table just the AWG column converted?
No. A mm² to AWG conversion is geometry only: it compares cross-sectional areas. The IEC capacities depend on insulation, installation method, ambient temperature and grouping, which is why they are printed as their own table. For the conversion itself, use the mm² to AWG chart.
Can I print it, or hand it to someone else?
Yes. The sheet is free, needs no signup and prints on landscape A4 or Letter; the PDF is generated in the browser, so nothing is uploaded. If you pass it on, a link back to this page is appreciated and keeps the version current.
How are the values produced?
Every cell is computed by this site's calculation engine from registered constants rather than typed by hand, so the page, the PDF and the calculators cannot drift apart. The methodology page lists each source, its clause and its review status.

Sources, clauses and review status for every constant are on the methodology page.

Use the numbers in a calculator

Prefer the numbers in context? The correction-factor guide works through the same table step by step.