200 Amp Wire Size
Recommended conductor sizes for a 200 A circuit under typical conditions (75°C terminations, 30°C ambient, three current-carrying conductors in the raceway). Adjust the conditions below for your job.
Quick answer
| Material | Minimum size | Ampacity at that size |
|---|---|---|
| Copper | 3/0 AWG/kcmil | 200 A |
| Aluminum | 250 AWG/kcmil | 205 A |
Calculator
Final ampacity
200 A
Required
200 A
Breaker
200 A
Calculation steps
- 基准载流量(75°C)200 ARef: NEC 310.16
- 环境温度 30°C 修正1Ref: NEC 310.15(B)(1)
- 同管 3 根修正1Ref: NEC 310.15(C)(1)
- 修正后载流量200 x 1 x 1200 A
- 端子温度限制(75°C)200 ARef: NEC 110.14(C)
- 最终允许载流量(取两者较小)200 A
- 所需电流200 ARef: NEC 210.20(A)
本工具结果仅供教育、设计规划与一般信息参考,不构成专业工程建议或持证安装建议。工程规范与电气法规因地区而异,实际安装必须由持证电工依据当地现行法规执行。误用计算结果可能导致电气火灾、设备损坏或违反法规。所有数值请自行核对现行 NEC 版本。
Notes for a 200 A circuit
- The size above assumes 75°C terminations. If the equipment is only rated 60°C, the usable ampacity drops.
- Long runs may need a larger conductor to stay within the 3% branch-circuit voltage drop recommendation — check with the voltage drop calculator.
- Conduit sizing for the chosen conductor is on the conduit fill chart.
Table values pending review against the current NEC edition. Not professional engineering advice.