Wire Ampacity Chart
How to read this chart
There is one ampacity per conductor per temperature column, and the column is set by the weakest link in the circuit — not by the conductor alone. The 90°C column is the insulation's own limit, so it applies only when the terminations are also rated 90°C. Equipment rated 100 A or less defaults to the 60°C column unless it is marked 75°C. Equipment over 100 A defaults to 75°C. A 90°C THHN conductor is governed by whichever of those columns the terminals require, not automatically by the 75°C column (NEC 110.14(C)).
Two corrections then move the number. Ambient temperature correction (NEC Table 310.15(B)(1)(1)) is applied when the surrounding air is not the 30°C the table assumes. The adjustment for more than three current-carrying conductors in a raceway (NEC 310.15(C)(1)) is applied when conductors share a raceway. The circuit may use the smaller of the corrected ampacity and the termination column.
Sizes of 250 kcmil and above are also written MCM in older references: 500 kcmil and 500 MCM are the same conductor, and 750 MCM is the same as 750 kcmil.
Copper
| Size | 60°C | 75°C | 90°C |
|---|---|---|---|
| 14 AWG | 15 A | 20 A | 25 A |
| 12 AWG | 20 A | 25 A | 30 A |
| 10 AWG | 30 A | 35 A | 40 A |
| 8 AWG | 40 A | 50 A | 55 A |
| 6 AWG | 55 A | 65 A | 75 A |
| 4 AWG | 70 A | 85 A | 95 A |
| 3 AWG | 85 A | 100 A | 115 A |
| 2 AWG | 95 A | 115 A | 130 A |
| 1 AWG | 110 A | 130 A | 145 A |
| 1/0 AWG | 125 A | 150 A | 170 A |
| 2/0 AWG | 145 A | 175 A | 195 A |
| 3/0 AWG | 165 A | 200 A | 225 A |
| 4/0 AWG | 195 A | 230 A | 260 A |
| 250 kcmil | 215 A | 255 A | 290 A |
| 300 kcmil | 240 A | 285 A | 320 A |
| 350 kcmil | 260 A | 310 A | 350 A |
| 400 kcmil | 280 A | 335 A | 380 A |
| 500 kcmil | 320 A | 380 A | 430 A |
| 600 kcmil | 350 A | 420 A | 475 A |
| 750 kcmil | 400 A | 475 A | 535 A |
| 1000 kcmil | 455 A | 545 A | 615 A |
Aluminum
| Size | 60°C | 75°C | 90°C |
|---|---|---|---|
| 12 AWG | 15 A | 20 A | 25 A |
| 10 AWG | 25 A | 30 A | 35 A |
| 8 AWG | 35 A | 40 A | 45 A |
| 6 AWG | 40 A | 50 A | 55 A |
| 4 AWG | 55 A | 65 A | 75 A |
| 3 AWG | 65 A | 75 A | 85 A |
| 2 AWG | 75 A | 90 A | 100 A |
| 1 AWG | 85 A | 100 A | 115 A |
| 1/0 AWG | 100 A | 120 A | 135 A |
| 2/0 AWG | 115 A | 135 A | 150 A |
| 3/0 AWG | 130 A | 155 A | 175 A |
| 4/0 AWG | 150 A | 180 A | 205 A |
| 250 kcmil | 170 A | 205 A | 230 A |
| 300 kcmil | 195 A | 230 A | 260 A |
| 350 kcmil | 210 A | 250 A | 280 A |
| 400 kcmil | 225 A | 270 A | 305 A |
| 500 kcmil | 260 A | 310 A | 350 A |
| 600 kcmil | 285 A | 340 A | 385 A |
| 750 kcmil | 320 A | 385 A | 435 A |
| 1000 kcmil | 375 A | 445 A | 500 A |
Aluminum conductor ampacity for common sizes
Aluminum is not a drop-in replacement for copper. At the same size it carries less current, so an aluminum run is usually one or two standard sizes larger than the copper run it replaces. Terminations must be listed for aluminum, and small branch-circuit sizes are commonly restricted, which is why aluminum shows up on service conductors, feeders and large feeders far more often than on 15 A or 20 A branch circuits.
| Size | 75°C | 90°C |
|---|---|---|
| 6 AWG | 50 A | 55 A |
| 4 AWG | 65 A | 75 A |
| 2 AWG | 90 A | 100 A |
| 1/0 AWG | 120 A | 135 A |
| 2/0 AWG | 135 A | 150 A |
| 4/0 AWG | 180 A | 205 A |
| 250 kcmil | 205 A | 230 A |
| 350 kcmil | 250 A | 280 A |
| 500 kcmil | 310 A | 350 A |
| 750 kcmil | 385 A | 435 A |
Base values only. Apply the same ambient and conductor-count corrections as copper, then compare against the termination rating: a 90°C aluminum conductor on a 75°C lug is still limited to the 75°C column.
Values reflect NEC 2023 and are pending review; the 2026 edition has not been verified. Verify before relying on them for construction.