What Size Wire for a 100 Amp Sub Panel?

A 100 A feeder is a standard size, but the conductor that carries it depends on three things people usually forget: the termination temperature rating, the ambient temperature, and how many current-carrying conductors share the raceway.

Quick answer

MaterialMinimum sizeAmpacity
Copper1 AWG110 A
Aluminum1/0 AWG100 A

Computed by this site's calculation engine for a 100 A load under 60°C terminations, the NEC default for equipment rated 100 A or less that is not marked 75°C; 30°C ambient; three current-carrying conductors. Table values are pending review against NEC 2023 — confirm with the wire size calculator before ordering cable. If the terminations are listed 75°C, the same load is copper 3 AWG or aluminum 1 AWG.

Why there is no single answer

The conductor has to satisfy two separate limits. First, its corrected ampacity must cover the load. Second, the termination it lands on caps how much of that ampacity you may actually use.

Equipment rated 100 A or less defaults to the 60°C column unless the terminals are listed for 75°C. The quick answer uses that default. Listed 75°C terminations are a smaller, separate case, shown under the table.

Work through it in order

Run the steps in this order every time:

  • Start from the load: a 100 A feeder with no continuous load is 100 A; add 25% for the continuous portion.
  • Pick an insulation temperature rating (THHN is typically 90°C, but you seldom get to use the 90°C column).
  • Apply the ambient correction factor for the actual temperature where the raceway runs.
  • Apply the conductor-count adjustment if more than three current-carrying conductors share the raceway.
  • Take the lower of the corrected ampacity and the termination-limited ampacity.
  • Choose the smallest standard size that still covers the load, then check voltage drop on the actual run length.

Do not forget voltage drop

A sub panel feeder is often long. Even a conductor that passes the ampacity check can exceed the 3% feeder voltage drop recommended in the informational note to NEC 215.2(A)(1), which pushes you one or two sizes up.

Check the run with the voltage drop calculator before you buy cable — upsizing after the fact is expensive.

Frequently asked

Does the sub panel need a grounding conductor?
A feeder to a separate structure is normally a four-wire feeder: two ungrounded conductors, one grounded conductor and one equipment grounding conductor. Grounding and bonding rules differ for separate structures, so confirm the arrangement with your local inspector.
Can I use aluminum for a 100 A feeder?
Aluminum is commonly used for feeders and terminations are listed for it, but aluminum carries less current than copper at the same size, so the required size is larger. Run the calculator for both and compare.
Is 100 A the breaker size or the calculated load?
They are different. Size the conductor for the calculated load and the overcurrent device for the circuit. A standard 100 A device is a common choice, but the conductor still has to carry the load after corrections.

Related calculators

Cite this page

Use this reference in a report, article, course note or dataset. Calculated examples use this site's engine; reference data and explanatory text have separate sources and review status.

ElecCalcs. “What Size Wire for a 100 Amp Sub Panel?.” Updated October 29, 2026. https://eleccalcs.com/guides/what-size-wire-for-100-amp-sub-panel

Values reflect NEC 2023 and are pending review. Cite the edition you verified against.