THHN vs THWN: What the Letters Mean
The letters describe the insulation: heat resistance, moisture resistance and where the conductor may be installed. The designation decides which temperature column you are allowed to use.
Decoding the letters
Each letter is a property:
- T — thermoplastic insulation.
- H — heat resistant, rated 75°C.
- HH — heat resistant to 90°C.
- W — moisture resistant, suitable for wet locations.
- N — nylon jacket, resistant to gasoline and oil.
Why THWN-2 is the practical default
THHN is dry-location only. THWN is wet-location rated but sometimes limited to 75°C. THWN-2 is both wet-location rated and good for 90°C, which is why it is so common in conduit.
The 90°C rating does not mean you get to run the conductor at 90°C ampacity. Terminations and equipment ratings usually cap you lower.
Frequently asked
- Can I use THHN outdoors?
- THHN alone is a dry-location conductor. In wet locations you need the W rating, which is why dual-rated THHN/THWN-2 is commonly used.
- If it is 90°C rated, can I use the 90°C ampacity?
- Usually not in full. The termination temperature limit can cap the usable ampacity, and the 90°C column is mainly useful for applying correction factors from a higher base.
- Does the insulation type change the diameter?
- Yes, different insulation types have different outside diameters, which changes how many conductors fit a raceway.